RISH Ducer : Current I11
 
Features :
  Designed and Tested to meet Requirements of IEC 688 and IS 12784
  Reliable SMD Technology
  High Insulation Level
  Higher load Capacity
  Easy onsite conversion between DIN rail or Panel Mounting
  Polycarbonate body, conforming to UL 94-VO
     
 
 Measuring Quantity
AC Current
 Nominal Input
1A or 5A
 Output Quantity
Independent DC Current or DC Voltage
 Output Range
0-1/0-5/0-10 or 0-20mA
4-20mA-2wire connection
0-1OV
 Ripple
<1% P-P
 Output Burden
Current Output : Rext = 15V / I (full Scale) [750@ 20mA or 1500@ 10mA]
Voltage Output : Rext = Output Voltage/ 20mA,
 Auxiliary supply
Self Powered OR
12V - 30V
(only for 2 wire connection with output 4 - 20mA)
 Power Consumption
-
 Response Time
< 300ms
 High Insulation Level
4 kV
 Impulse withstand  Voltage
5kV, 1.2/50 µsec, 0.5 Ws.
 Accuracy as per IEC 688
Class 0.5
 Operating Temperature
-25 to 55°C
   
  - M42
  - M24
  - M40
  - M01
  - M20
  - Configuration Software MXX
  - I 11
  - I 12
  - E 15
  - E 1D
  - E 13
  - I 21
  - I 22
  - V 11
  - E 15
  - E 1D
  - E 13
  - V 21
  - V 22
  - F 11
  - F 12
  - P11- Active/Reactive
  - C11-Powe Factor/Phase Angle
  - C12- Phase angle difference