RISH Ducer : Frequency F12
 
Features :
  Designed and Tested to meet Requirements of IEC 688 and IS 12784
  Reliable SMD Technology
  High Insulation Level
  Higher load Capacity
  Easy onsite conversion between DIN rail or Panel Mounting
  Polycarbonate body, conforming to UL 94-VO
     
 
Measuring Quantity
Frequency
Nominal Input
63.5V...480V 45-55Hz/55-65Hz/ 45 - 65Hz/360Hz-440Hz
Output Quantity
Independent DC Current or DC Voltage
Output Range
0-1/ 0-5/0-10/0-20mA/
4-20mA
0-5/10V
Option : Dual Output
Ripple
<5% of full rated output
Output Burden
Current Output : Rext = 15V / I (full Scale) [750 @ 20mA or 1500 @ 10mA]
Voltage Output : Rext = Output Voltage/ 20mA,
Auxiliary supply
AC: 24/110/120/230/380V DC 24...60V AC/DC or 85...230V AC/DC
Power Consumption
< 2VA
Response Time
< 400ms
High Insulation Level
3.7 kV
Impulse withstand Voltage
5kV, 1.2/50 µsec, 0.5 Ws.
Accuracy as per IEC 688
Class 0.2
Operating Temperature
0 to 60 °C
     
   
  - M42
  - M24
  - M40
  - M01