Programmable universal transmitter RISHDucer V604, converts the input variable- a DC current or voltage, or a signal from a thermocouple, resistance thermometer, remote sensor or potentiometer - to a proportional analog output signal.
Features :
•
Input variable (Resistance, DC current, DC voltage, Potentiometer)
and all measuring ranges programmed using PC.
•
Output signal range and characteristics(linear/bent/live zero) are
programmed using PC and the type of output signal (current or
voltage) on a DIP switch.
•
Electrical isolation between measured variable, analog output signal
and power supply as per EN 6 1010
•
Measured variable data available at the programming interface.
•
Measured variable and signals can be viewed on site using a PC.
Measuring Input :
B, E, J, K, L, N, R, S, T, U W5 - W26 Re
Pt 100, Ni 100, Pt 20/20 °C , Cu 10/25 °C, Cu 20 / 25 °C,
2,3 or 4wire connection
0...8Ω to 0....5kΩ
0...80m A to 0...100 mA
0...2 mV to 0...40 V
Cold Junction compensation
Internal : Incorporated resistor Ni 100
DC current :
Ranges
0 ... 20 or 4 ... 20 mA limit ± 22mA
Burden Voltage
+15 V, resp - 12v
DC voltage :
Ranges
0... 5, 1 ...5, 0...10 or 2... 10V
limit
12V to + 15V
Load capacity
20mA
Power Supply
24 V . . . 60 V DC/AC and 85 V . . . 230 V DC/AC
Accuracy
± 0.5%
Inputs & Outputs available
1 input - 2 outputs
LED Display :
Green LED
For indicating device in operating condition
Red LED
For indicating operation of open-circuit or trip point